The Work
A gang operated disconnector — the AB switch on the pole, worked from an operating handle at ground level — is how an overhead HT line is isolated and sectionalised. It is what lets a crew take an outage on one spur instead of the whole feeder, and what makes a transformer safe to work on without waiting for the utility to switch upstream.
The work is mechanical as much as electrical. All three blades have to close together and fully, the operating pipe and linkage have to move freely after a monsoon, the structure has to be rigid enough that the line pull does not twist the frame, and the whole assembly has to be earthed. A G.O.D that half-closes is worse than none — it arcs, and it gives a false sense of isolation.